Skip to content
CutronexAutomation Reference
Browse standards

M12 A-, D- and X-coded connectors

Use the coding and pinout specified on the equipment drawing. A-coded variants are common for sensor and actuator connections, D-coded variants for two-pair industrial Ethernet, and X-coded variants for four-pair Ethernet.

Compare the options

ReferenceWhere it appliesWhat to verify
M12 A-Coded Connector (IEC 61076-2-101)Sensor and actuator connections, including products with different contact counts and signal assignments.Match the number of contacts, connector gender, and equipment pinout. A four-contact A-coded plug and a four-contact D-coded plug use different keying.
M12 D-Coded Connector (IEC 61076-2-101)Four-contact, two-pair industrial Ethernet connections, commonly used for 100 Mb/s links.Check the port coding, pin assignment, shield connection, and approved cable assembly.
M12 X-Coded Connector (IEC 61076-2-109)Eight-contact, four-pair Ethernet connections, with suitable Cat 6A assemblies supporting 10 Gb/s.Check the cable assembly category and the speed supported by both device ports.

Before you specify

  • Record coding, gender, contact count, and pin assignment independently.
  • Check the mated ingress rating and installation details on the exact cordset and port.

Sources