What is M12 A-Coded Connector (IEC 61076-2-101)?

The M12 A-coded circular connector (IEC 61076-2-101) is the primary industrial interface for DC sensors, actuators, IO-Link devices, and DeviceNet/CANopen buses, featuring an M12x1 locking thread and a single anti-rotation keyway.

  • Match coding, contact count, and pinout on both mating parts.

What are the key specifications?

See the source publications and editions

ParameterSpecification
Governing StandardIEC 61076-2-101 (A-coding)
Pin Counts3, 4, 5, 8, and 12 poles
Rated Voltage (typical)250 V (3/4-pin), 60 V (5-pin), 30 V (8/12-pin)
Rated Current (typical)4 A per contact (3/4/5-pin); 2 A (8-pin); 1.5 A (12-pin)
Standard Wire Colors (4-pin)1=Brown (+24V), 2=White (Aux), 3=Blue (0V), 4=Black (Signal/C/Q)
Ingress Rating (Mated)IP65 / IP67 (up to IP69K with hygienic overmold)

Sources and scope

IEC 61076-2-101 Ed. 3.0 Connectors for electronic equipment — Circular connectors — Detail specification for M12 connectors with screw-locking.

Record date:

Suggest a correction

Where is it used?

  • Connecting inductive, capacitive, photoelectric, and ultrasonic sensors to PLC I/O blocks.
  • Point-to-point IO-Link Class A and Class B sensor/actuator links.
  • CANopen and DeviceNet drop cables (typically 5-pin configuration).

What are the common pitfalls?

  • Overloading 4 A A-coded contacts with high-current actuator power instead of M12 L-coded or 7/8" power connectors.
  • Using unshielded 4-pin sensor cordsets for analog 4–20 mA or CAN signals in noisy VFD environments.
  • Hand-tightening plastic locknuts without a torque wrench (0.6 Nm) leads to vibration loosening and IP67 seal loss.