What is 0–10 V DC Analog Control Signal (IEC 60381-2)?
The 0–10 V DC analog standard (IEC 60381-2) represents continuous setpoint or feedback quantities as a ground-referenced DC voltage, widely used for short-run VFD speed references, proportional valves, and building HVAC dampers.
What are the key specifications?
| Parameter | Specification |
|---|---|
| Governing Standard | IEC 60381-2 (Analogue signals — Direct voltage signals) |
| Nominal Signal Range | 0.0 V DC (0%) to +10.0 V DC (100%) |
| Input Impedance (Receiver) | Typically >= 10 kOhm to 100 kOhm |
| Cable Run Practical Limit | Short runs (typically < 15–30 m shielded) due to EMI & ground offset |
| Fault Detection | None natively (0 V equals both 0% scale and broken wire) |
Sources and scope
IEC 60381-2 Analogue signals for process control systems — Part 2: Direct voltage signals.
Record date:
Where is it used?
- Inside-cabinet or short machine-harness speed commands to VFDs and servo amplifiers.
- Proportional pressure regulators and proportional flow control valve command inputs.
- HVAC damper actuators, variable air volume controllers, and industrial dimmers.
What are the common pitfalls?
- 0 V cannot distinguish between a legitimate zero setpoint and a broken wire or powered-off sensor (unlike 4–20 mA or 2–10 V).
- Running unshielded 0–10 V lines parallel to PWM motor cables induces significant signal jitter.
- Voltage drop on shared 0 V return conductors carrying actuator coil current corrupts the analog reference voltage.