What is 0–10 V DC Analog Control Signal (IEC 60381-2)?

The 0–10 V DC analog standard (IEC 60381-2) represents continuous setpoint or feedback quantities as a ground-referenced DC voltage, widely used for short-run VFD speed references, proportional valves, and building HVAC dampers.

What are the key specifications?

ParameterSpecification
Governing StandardIEC 60381-2 (Analogue signals — Direct voltage signals)
Nominal Signal Range0.0 V DC (0%) to +10.0 V DC (100%)
Input Impedance (Receiver)Typically >= 10 kOhm to 100 kOhm
Cable Run Practical LimitShort runs (typically < 15–30 m shielded) due to EMI & ground offset
Fault DetectionNone natively (0 V equals both 0% scale and broken wire)

Sources and scope

IEC 60381-2 Analogue signals for process control systems — Part 2: Direct voltage signals.

Record date:

Suggest a correction

Where is it used?

  • Inside-cabinet or short machine-harness speed commands to VFDs and servo amplifiers.
  • Proportional pressure regulators and proportional flow control valve command inputs.
  • HVAC damper actuators, variable air volume controllers, and industrial dimmers.

What are the common pitfalls?

  • 0 V cannot distinguish between a legitimate zero setpoint and a broken wire or powered-off sensor (unlike 4–20 mA or 2–10 V).
  • Running unshielded 0–10 V lines parallel to PWM motor cables induces significant signal jitter.
  • Voltage drop on shared 0 V return conductors carrying actuator coil current corrupts the analog reference voltage.