What is 4–20 mA Analog Current Loop (IEC 60381-1 / NAMUR NE 43)?
The 4–20 mA analog current loop (IEC 60381-1) transmits continuous process or control values as a proportional DC current insensitive to wire resistance voltage drops, with live-zero (4 mA) enabling broken-wire detection and optional NAMUR NE 43 fault bands.
What are the key specifications?
| Parameter | Specification |
|---|---|
| Governing Standards | IEC 60381-1 & NAMUR NE 43 (Fault Signal Levels) |
| Normal Measuring Range | 4.0 mA (0% scale) to 20.0 mA (100% scale) |
| NAMUR NE 43 Fault Bands | <= 3.6 mA (low fault / open wire) or >= 21.0 mA (high fault) |
| Loop Configurations | 2-wire loop-powered (passive) or 4-wire externally powered (active) |
| Typical Input Shunt | 250 ohm (1–5 V) or 500 ohm (2–10 V) at PLC AI card |
| Noise & Distance | High EMI immunity; runs > 1,000 m subject to supply compliance voltage |
Sources and scope
IEC 60381-1 Analogue signals for process control systems — Part 1: Direct current signals, and NAMUR NE 43.
Record date:
Where is it used?
- Process pressure, level, flow, and RTD/thermocouple transmitter loops.
- Command signals for proportional hydraulic/pneumatic valves and I/P transducers.
- Safety-related analog measurements requiring wire-break diagnostics via 4 mA live zero.
What are the common pitfalls?
- Connecting a 2-wire loop-powered transmitter directly to a 4-wire active PLC input without loop power (or vice versa, causing short circuits).
- Exceeding total loop burden resistance (wire + AI card + IS barrier) causes signal saturation below 20 mA.
- Omitting galvanic loop isolators when grounding multiple non-isolated PLC inputs causes ground-loop drift.