What is 4–20 mA Analog Current Loop (IEC 60381-1 / NAMUR NE 43)?

The 4–20 mA analog current loop (IEC 60381-1) transmits continuous process or control values as a proportional DC current insensitive to wire resistance voltage drops, with live-zero (4 mA) enabling broken-wire detection and optional NAMUR NE 43 fault bands.

What are the key specifications?

ParameterSpecification
Governing StandardsIEC 60381-1 & NAMUR NE 43 (Fault Signal Levels)
Normal Measuring Range4.0 mA (0% scale) to 20.0 mA (100% scale)
NAMUR NE 43 Fault Bands<= 3.6 mA (low fault / open wire) or >= 21.0 mA (high fault)
Loop Configurations2-wire loop-powered (passive) or 4-wire externally powered (active)
Typical Input Shunt250 ohm (1–5 V) or 500 ohm (2–10 V) at PLC AI card
Noise & DistanceHigh EMI immunity; runs > 1,000 m subject to supply compliance voltage

Sources and scope

IEC 60381-1 Analogue signals for process control systems — Part 1: Direct current signals, and NAMUR NE 43.

Record date:

Suggest a correction

Where is it used?

  • Process pressure, level, flow, and RTD/thermocouple transmitter loops.
  • Command signals for proportional hydraulic/pneumatic valves and I/P transducers.
  • Safety-related analog measurements requiring wire-break diagnostics via 4 mA live zero.

What are the common pitfalls?

  • Connecting a 2-wire loop-powered transmitter directly to a 4-wire active PLC input without loop power (or vice versa, causing short circuits).
  • Exceeding total loop burden resistance (wire + AI card + IS barrier) causes signal saturation below 20 mA.
  • Omitting galvanic loop isolators when grounding multiple non-isolated PLC inputs causes ground-loop drift.