Skip to content
CutronexAutomation Reference

What is ATEX Directive 2014/34/EU (Zone 2 / Zone 22)?

ATEX Directive 2014/34/EU governs equipment intended for potentially explosive gas or dust atmospheres in the European market; Category 3 equipment (3G / 3D) is rated for Zone 2 (infrequent/short gas hazard) and Zone 22 (infrequent/short combustible dust hazard).

What are the key specifications?

ParameterSpecification
Governing DirectiveEU ATEX Directive 2014/34/EU (Equipment) & 1999/92/EC (Workplace)
Zone 2 (Gas - Category 3G)Explosive gas/vapor unlikely in normal operation, short duration if present
Zone 22 (Dust - Category 3D)Explosive combustible dust cloud unlikely, short duration if present
Common Protection ConceptsEx ec (increased safety), Ex nA/nR, Ex ic (intrinsic safety), Ex tc (enclosure)
Example MarkingII 3G Ex ec IIC T4 Gc / II 3D Ex tc IIIC T135°C Dc
Conformity Route (Cat 3)Internal production control (Module A) + EU DoC (Notified Body optional for Cat 3)

Sources and scope

Directive 2014/34/EU (ATEX) and EN IEC 60079-0 / -7 / -15 / -31.

Record date:

Suggest a correction

Where is it used?

  • Specifying field sensors, solenoid valves, and remote I/O in grain silos, flour mills, and pharmaceutical powder zones (Zone 22).
  • Instrumentation around paint booths, solvent storage manifolds, and natural gas skids (Zone 2).
  • Matching Temperature Class (T1–T6) below the auto-ignition temperature of the process chemical.

What are the common pitfalls?

  • Installing Category 3 (Zone 2/22) hardware inside Zone 1/21 or Zone 0/20 areas (requires Category 2 or Category 1 with Notified Body EU Type Examination).
  • Forgetting mechanical connector locking clips/guards on M12 or DIN plugs in Zone 2/22 where ATEX prohibits disconnection under load.
  • Overlooking conductive dust group IIIC vs. non-conductive IIIB when selecting Ex tc IP6X enclosure tolerances.