What is IECEx System (IEC 60079 Series)?
The IECEx System is an international voluntary certification scheme based on the IEC 60079 standard series that verifies equipment safety in explosive gas (Groups IIA/IIB/IIC) and dust (Groups IIIA/IIIB/IIIC) atmospheres across participating countries.
What are the key specifications?
| Parameter | Specification |
|---|---|
| Governing Standards | IEC 60079 Series (IEC 60079-0, -1, -7, -11, -15, -31) |
| Equipment Protection Levels | Ga/Da (Zone 0/20), Gb/Db (Zone 1/21), Gc/Dc (Zone 2/22) |
| Key Ex Types | Ex d (flameproof), Ex e (increased safety), Ex i (intrinsic safety), Ex m (encapsulation) |
| Certificate Components | IECEx CoC (Certificate of Conformity), ExTR (Test Report), QAR (Quality Assessment) |
| Verification Database | Publicly auditable online at iecex.com |
Sources and scope
IECEx 02 Equipment Certification Scheme Rules and IEC 60079-0.
Record date:
Where is it used?
- Standardizing hazardous-area instrumentation across global EPC projects in Australia, Middle East, Asia, and Europe.
- Confirming intrinsic safety entity parameters (Ui, Ii, Pi, Ci, Li) between field sensors and safety barriers.
- Auditing valid Ex certificates and Special Conditions of Safe Use ('X' suffix) before procurement.
What are the common pitfalls?
- Assuming an IECEx certificate alone replaces mandatory EU ATEX CE marking or North American NEC/UL listings without regional acceptance.
- Ignoring the 'X' suffix on an IECEx certificate number, which indicates mandatory Special Conditions for Safe Use (e.g., restricted ambient temp or electrostatic wipe warnings).