What is NAMUR Sensor Interface (IEC 60947-5-6) & NE 21?
IEC 60947-5-6 (NAMUR) specifies a 2-wire DC low-energy proximity sensor interface operating around 8.2 V DC with distinct current thresholds (<= 1.2 mA vs. >= 2.1 mA) for intrinsic safety barriers, complemented by NAMUR NE 21 EMC requirements for process instruments.
What are the key specifications?
| Parameter | Specification |
|---|---|
| Governing Standards | IEC 60947-5-6 (formerly DIN 19234) & NAMUR NE 21 (EMC) |
| Nominal Supply Voltage | 8.2 V DC (via isolated switching amplifier with 1 kOhm internal impedance) |
| Switching Current States | Damped/Low: <= 1.2 mA; Undamped/High: >= 2.1 mA |
| Line Fault Detection | Open circuit (< 0.05–0.1 mA) and short circuit (> 6–6.5 mA) detected |
| Hazardous Area Advantage | Very low stored energy enables Ex ia Zone 0/1/20 certification |
Sources and scope
IEC 60947-5-6 DC interface for proximity sensors and switching amplifiers (NAMUR), and NAMUR Recommendation NE 21.
Record date:
Where is it used?
- Valve-position feedback and turbine/pump speed sensors inside chemical reactors and tank farms (Ex ia).
- Safety-critical SIL 2 / SIL 3 process interlocks utilizing line-fault detection on switching amplifiers.
- High-EMC-reliability process transmitters qualified under NAMUR NE 21.
What are the common pitfalls?
- Connecting a 2-wire 8.2 V NAMUR sensor directly to a standard 24 V DC PLC digital input destroys the sensor electronics.
- Omitting the isolated NAMUR switch amplifier/barrier breaks line-break and short-circuit diagnostics.
- Exceeding intrinsically safe cable capacitance/inductance limits (Co / Lo) on long barrier field runs.