What is Modbus RTU?
Modbus RTU is a compact binary serial communication protocol operating in a single-master/multi-slave architecture typically over EIA/TIA-485 two-wire differential links using 16-bit CRC error checking.
- Match serial settings and device address before testing the register map.
What are the key specifications?
See the source publications and editions
| Parameter | Specification |
|---|---|
| Physical Layer | RS-485 (2-wire or 4-wire) or RS-232 (point-to-point) |
| Framing | Binary RTU with 3.5-character silent interval frame delimiter |
| Common Baud Rates | 9,600 / 19,200 / 38,400 / 115,200 bps |
| Addressing Range | Slave IDs 1–247 (0 reserved for broadcast) |
| Error Detection | 16-bit Cyclic Redundancy Check (CRC-16) |
| Max Bus Length (RS-485) | Up to 1,200 m at <= 93.75 kbps without repeaters |
Sources and scope
Modbus Organization MODBUS over Serial Line Specification and Implementation Guide V1.02.
Record date:
Where is it used?
- Reading energy meters, power monitors, and temperature controllers in MCC panels.
- Basic speed reference and fault-status polling on variable frequency drives (VFDs).
- Integrating legacy PLC/RTU field instrumentation into modern SCADA gateways.
What are the common pitfalls?
- Mismatched 1-based register numbering vs. 0-based protocol offsets (e.g., 40001 vs. PDU offset 0x0000).
- Inconsistent 32-bit float/double word order (big-endian vs. little-endian word swap) across vendors.
- Using non-twisted unshielded hookup wire or omitting 120-ohm termination resistors at both bus ends.
- Connecting D+/D- polarity backwards between devices from different manufacturers.