CutronexAutomation Reference

What is Modbus RTU?

Modbus RTU is a compact binary serial communication protocol operating in a single-master/multi-slave architecture typically over EIA/TIA-485 two-wire differential links using 16-bit CRC error checking.

  • Match serial settings and device address before testing the register map.

What are the key specifications?

See the source publications and editions

ParameterSpecification
Physical LayerRS-485 (2-wire or 4-wire) or RS-232 (point-to-point)
FramingBinary RTU with 3.5-character silent interval frame delimiter
Common Baud Rates9,600 / 19,200 / 38,400 / 115,200 bps
Addressing RangeSlave IDs 1–247 (0 reserved for broadcast)
Error Detection16-bit Cyclic Redundancy Check (CRC-16)
Max Bus Length (RS-485)Up to 1,200 m at <= 93.75 kbps without repeaters

Sources and scope

Modbus Organization MODBUS over Serial Line Specification and Implementation Guide V1.02.

Record date:

Suggest a correction

Where is it used?

  • Reading energy meters, power monitors, and temperature controllers in MCC panels.
  • Basic speed reference and fault-status polling on variable frequency drives (VFDs).
  • Integrating legacy PLC/RTU field instrumentation into modern SCADA gateways.

What are the common pitfalls?

  • Mismatched 1-based register numbering vs. 0-based protocol offsets (e.g., 40001 vs. PDU offset 0x0000).
  • Inconsistent 32-bit float/double word order (big-endian vs. little-endian word swap) across vendors.
  • Using non-twisted unshielded hookup wire or omitting 120-ohm termination resistors at both bus ends.
  • Connecting D+/D- polarity backwards between devices from different manufacturers.