What is HART Protocol (IEC 61158 / FieldComm)?
HART (Highway Addressable Remote Transducer) superimposes a 1,200 bps Frequency Shift Keying (FSK) digital signal onto a standard 4–20 mA analog loop, allowing bidirectional diagnostics and calibration without interrupting the primary analog process variable.
What are the key specifications?
| Parameter | Specification |
|---|---|
| Governing Standard | IEC 61158 / FieldComm Group HART Specification (Rev 7) |
| Modulation | Bell 202 FSK (1,200 Hz = logic 1; 2,200 Hz = logic 0) +/-0.5 mA |
| Bit Rate | 1,200 bps half-duplex |
| Loop Resistance | 230 – 600 ohm total loop resistance (minimum 230–250 ohm for FSK) |
| Max Cable Length | Up to 1,500–3,000 m depending on cable capacitance & shield |
| Wireless Variant | WirelessHART (IEC 62591, IEEE 802.15.4 2.4 GHz mesh) |
Sources and scope
FieldComm Group HART Communication Protocol Specification and IEC 61158.
Record date:
Where is it used?
- Commissioning, zeroing, and diagnosing smart pressure, temperature, and Coriolis flow transmitters.
- Multivariable monitoring (e.g., reading flow on 4–20 mA while polling density and temperature digitally).
- Intrinsically safe hazardous-area process loops using isolated HART-transparent barriers.
What are the common pitfalls?
- Using non-HART-compatible intrinsic safety barriers that short out the 1,200/2,200 Hz FSK carrier.
- Insufficient loop series resistance (< 230 ohm) prevents handheld communicators from reading FSK voltage modulation.
- High cable capacitance on excessively long runs attenuates the 2,200 Hz FSK tone.