What is TIA/EIA-485 (RS-485)?

TIA/EIA-485 (RS-485) defines the balanced differential electrical characteristics of drivers and receivers for multi-point serial industrial buses, enabling noise-immune data transmission over long twisted-pair runs.

What are the key specifications?

ParameterSpecification
Governing StandardANSI/TIA/EIA-485-A
Signaling MethodBalanced differential voltage (+/-1.5 V to +/-5 V loaded)
Common-Mode Range-7 V to +12 V receiver tolerance
Unit Loads32 standard unit loads (up to 128 or 256 with 1/4 or 1/8 UL transceivers)
Cable Impedance120 ohm nominal twisted pair (150 ohm for PROFIBUS)
Max DistanceUp to 1,200 m at <= 100 kbps (derates linearly with higher baud rates)

Sources and scope

ANSI/TIA/EIA-485-A Electrical Characteristics of Generators and Receivers for Use in Balanced Digital Multipoint Systems.

Record date:

Suggest a correction

Where is it used?

  • Underlying physical layer for Modbus RTU, PROFIBUS DP, DMX512, and BACnet MS/TP.
  • Long-distance sensor telemetry across noisy VFD and motor-drive plant floors.
  • Point-to-multipoint barcode scanner, weigh scale, and panel meter serial loops.

What are the common pitfalls?

  • Running only 2 wires (A/B) without a signal common reference wire or proper isolated transceivers across large ground potential differences.
  • Wiring star topologies instead of a true linear daisy chain, introducing impedance discontinuities.
  • Omitting fail-safe bias resistors on idle half-duplex buses, causing spurious framing errors.