What is TIA/EIA-485 (RS-485)?
TIA/EIA-485 (RS-485) defines the balanced differential electrical characteristics of drivers and receivers for multi-point serial industrial buses, enabling noise-immune data transmission over long twisted-pair runs.
What are the key specifications?
| Parameter | Specification |
|---|---|
| Governing Standard | ANSI/TIA/EIA-485-A |
| Signaling Method | Balanced differential voltage (+/-1.5 V to +/-5 V loaded) |
| Common-Mode Range | -7 V to +12 V receiver tolerance |
| Unit Loads | 32 standard unit loads (up to 128 or 256 with 1/4 or 1/8 UL transceivers) |
| Cable Impedance | 120 ohm nominal twisted pair (150 ohm for PROFIBUS) |
| Max Distance | Up to 1,200 m at <= 100 kbps (derates linearly with higher baud rates) |
Sources and scope
ANSI/TIA/EIA-485-A Electrical Characteristics of Generators and Receivers for Use in Balanced Digital Multipoint Systems.
Record date:
Where is it used?
- Underlying physical layer for Modbus RTU, PROFIBUS DP, DMX512, and BACnet MS/TP.
- Long-distance sensor telemetry across noisy VFD and motor-drive plant floors.
- Point-to-multipoint barcode scanner, weigh scale, and panel meter serial loops.
What are the common pitfalls?
- Running only 2 wires (A/B) without a signal common reference wire or proper isolated transceivers across large ground potential differences.
- Wiring star topologies instead of a true linear daisy chain, introducing impedance discontinuities.
- Omitting fail-safe bias resistors on idle half-duplex buses, causing spurious framing errors.