What is IO-Link (IEC 61131-9)?
IO-Link (IEC 61131-9) is a standardized 24 V DC point-to-point serial communication protocol that exchanges cyclic process data, acyclic device parameters, and diagnostic events between an IO-Link master and field sensors or actuators over standard unshielded 3-wire or 5-wire cables.
- Match the master port class and device wiring.
- Confirm the IODD for the exact device and revision.
What are the key specifications?
See the source publications and editions
| Parameter | Specification |
|---|---|
| Governing Standard | IEC 61131-9 (Single-drop digital communication interface) |
| Topology | Point-to-point between IO-Link master port and 1 device |
| Data Rates | COM1 (4.8 kbps), COM2 (38.4 kbps), COM3 (230.4 kbps) |
| Max Cable Length | 20 m (unshielded standard sensor cable) |
| Signal Voltage | 24 V DC nominal (Pin 4 C/Q data line) |
| Port Classes | Class A (max 200 mA sensor supply) / Class B (galvanically isolated aux power) |
| Device Description | IODD (IO Device Description XML file) |
Sources and scope
IEC 61131-9 Ed. 2.0 and IO-Link Consortium Interface & System Specification v1.1.3.
Record date:
Where is it used?
- Replacing analog 4–20 mA sensor wiring with digital process values and remote parameter download.
- Automated recipe changeover on packaging machines where sensor switchpoints update via PLC.
- Condition monitoring of solenoid valve coils, smart light towers, and inductive proximity switches.
- Rapid device replacement using IO-Link Master parameter data storage without manual teaching.
What are the common pitfalls?
- Exceeding the 20 m point-to-point cable limit degrades COM3 (230.4 kbps) wake-up pulses and frame timing.
- Plugging a Class B actuator into a Class A master port leaves Pins 2 and 5 unpowered for isolated actuator loads.
- Omitting vendor IODD file alignment causes byte-swap or scaling mismatches when mapping cyclic process data.
- Treating IO-Link as a multi-drop fieldbus; each device strictly requires a dedicated IO-Link master port.