What is AS-Interface / AS-i (IEC 62026-2)?
AS-Interface (AS-i) is a two-wire electromechanical fieldbus standardized under IEC 62026-2 that transmits both modulated data and 29.5–31.6 V DC power over an unshielded keyed yellow flat cable via insulation-piercing taps.
What are the key specifications?
| Parameter | Specification |
|---|---|
| Governing Standard | IEC 62026-2 / AS-International Specification |
| Bus Voltage | 29.5 – 31.6 V DC (requires dedicated AS-i decoupled power supply) |
| Max Cable Length | 100 m standard (up to 300 m with repeater/passive extender) |
| Addressing Capacity | 31 standard slaves or 62 A/B slaves (AS-i v2.1/v3.0) |
| Cycle Time | 5 ms (31 slaves) / 10 ms (62 A/B slaves) |
| Physical Medium | Keyed trapezoidal 2-wire yellow flat cable (aux 24 V black cable) |
Sources and scope
IEC 62026-2 and AS-International Complete Specification v3.0.
Record date:
Where is it used?
- Long warehouse conveyor zones connecting photoeyes and motorized roller controls.
- Process valve manifolds and tank farms requiring simple binary open/closed position feedback.
- Safety-at-Work emergency stop and interlock chains wired onto existing AS-i trunks.
What are the common pitfalls?
- Powering an AS-i bus with an ordinary 24 V DC power supply instead of an AS-i data-decoupled 30 V DC supply destroys communication modulation.
- Neglecting to seal pierced yellow flat-cable tap punctures or exposed cut ends in washdown areas.
- Connecting standard round M12 sensors without AS-i slave electronics directly onto the bus.