Skip to content
CutronexAutomation Reference

What is PNP / NPN 24V DC Digital I/O (IEC 61131-2)?

IEC 61131-2 defines standardized voltage switching thresholds, current draw, and Type 1/2/3 input characteristics for 24 V DC PLC digital I/O, governing compatibility with PNP (current-sourcing) and NPN (current-sinking) field sensors.

What are the key specifications?

ParameterSpecification
Governing StandardIEC 61131-2 (Programmable controllers — Equipment requirements and tests)
Nominal Supply24 V DC (-15% / +20%, i.e., 20.4 – 28.8 V DC)
PNP (Sourcing) SensorSwitches +24 V DC to output load (connected to sinking PLC input)
NPN (Sinking) SensorSwitches 0 V / Common to output load (connected to sourcing PLC input)
Type 3 Input ThresholdsOFF <= 5 V (<= 1.5 mA); ON >= 11 V (>= 2 mA)
Type 1 Input ThresholdsOFF <= 5 V; ON >= 15 V (legacy mechanical contacts)

Sources and scope

IEC 61131-2 Ed. 4.0 Clause 5.2 Digital inputs and outputs.

Record date:

Suggest a correction

Where is it used?

  • Interfacing discrete 3-wire proximity, optical, and pressure switches with PLC digital input modules.
  • Selecting push-pull (PP) outputs that operate in both PNP/NPN and IO-Link SIO modes.
  • Ensuring 2-wire sensors with residual off-state leakage current do not falsely trigger Type 3 PLC inputs.

What are the common pitfalls?

  • Connecting a PNP sensor to a sourcing-only (NPN-expecting) PLC input card produces zero signal.
  • Mixing 2-wire sensors (up to 1.5–2.0 mA leakage current) with sensitive Type 3 PLC inputs keeps inputs permanently ON without a parallel bleeder resistor.
  • Shorting an unprotected NPN output to +24 V or failing to observe European (PNP dominant) vs. legacy Asian (NPN) machine standards.