Skip to content
CutronexAutomation Reference

What is M12 B-Coded Connector (IEC 61076-2-101)?

The M12 B-coded circular connector (IEC 61076-2-101) uses a reverse-keyed mechanical polarization to isolate PROFIBUS DP, Interbus, and RS-485 fieldbus trunks from standard A-coded DC sensor wiring.

What are the key specifications?

ParameterSpecification
Governing StandardIEC 61076-2-101 (B-coding)
Pin Count5-pin (commonly pins 2 & 4 for PROFIBUS data B/A, pin 5 shield)
Rated Voltage / Current60 V AC/DC, 4 A per contact (typical)
Characteristic Impedance150 ohm (when paired with PROFIBUS Type A cable)
Mechanical KeyingReverse-keyed boss prevents mating with A, D, or X-coded plugs
Ingress Rating (Mated)IP65 / IP67

Sources and scope

IEC 61076-2-101 and PI PROFIBUS Interconnection Technology Guideline.

Record date:

Suggest a correction

Where is it used?

  • On-machine IP67 PROFIBUS DP distributed I/O modules and rotary encoders.
  • Field-level RS-485 / Modbus RTU daisy-chain connections outside electrical panels.
  • Legacy Interbus fieldbus links requiring mechanical keying isolation.

What are the common pitfalls?

  • Omitting an M12 B-coded active terminating resistor plug at the final PROFIBUS DP slave causes bus reflection faults.
  • Ordering A-coded cordsets by mistake; A-coded connectors physically cannot mate with B-coded ports.
  • Pin 5 shield disconnection or miswiring PROFIBUS Pin 2 (Green/A) and Pin 4 (Red/B) polarity.