What is M12 B-Coded Connector (IEC 61076-2-101)?
The M12 B-coded circular connector (IEC 61076-2-101) uses a reverse-keyed mechanical polarization to isolate PROFIBUS DP, Interbus, and RS-485 fieldbus trunks from standard A-coded DC sensor wiring.
What are the key specifications?
| Parameter | Specification |
|---|---|
| Governing Standard | IEC 61076-2-101 (B-coding) |
| Pin Count | 5-pin (commonly pins 2 & 4 for PROFIBUS data B/A, pin 5 shield) |
| Rated Voltage / Current | 60 V AC/DC, 4 A per contact (typical) |
| Characteristic Impedance | 150 ohm (when paired with PROFIBUS Type A cable) |
| Mechanical Keying | Reverse-keyed boss prevents mating with A, D, or X-coded plugs |
| Ingress Rating (Mated) | IP65 / IP67 |
Sources and scope
IEC 61076-2-101 and PI PROFIBUS Interconnection Technology Guideline.
Record date:
Where is it used?
- On-machine IP67 PROFIBUS DP distributed I/O modules and rotary encoders.
- Field-level RS-485 / Modbus RTU daisy-chain connections outside electrical panels.
- Legacy Interbus fieldbus links requiring mechanical keying isolation.
What are the common pitfalls?
- Omitting an M12 B-coded active terminating resistor plug at the final PROFIBUS DP slave causes bus reflection faults.
- Ordering A-coded cordsets by mistake; A-coded connectors physically cannot mate with B-coded ports.
- Pin 5 shield disconnection or miswiring PROFIBUS Pin 2 (Green/A) and Pin 4 (Red/B) polarity.