What is PROFIBUS DP (IEC 61158 Type 3)?

PROFIBUS DP (Decentralized Periphery) is a deterministic RS-485 fieldbus standardized in IEC 61158 Type 3 for cyclic data exchange between PLC masters and distributed I/O, drives, and actuators at speeds up to 12 Mbps.

What are the key specifications?

ParameterSpecification
Governing StandardIEC 61158 Type 3 / IEC 61784-1 CPF 3
Physical LayerRS-485 shielded twisted pair (Type A, 150 ohm impedance)
Baud Rates9.6 kbps up to 12 Mbps (distance dependent)
Segment Length Limits1,200 m @ 93.75 kbps; 400 m @ 500 kbps; 100 m @ 12 Mbps
Max Stations / Segment32 devices per segment (up to 126 addresses via repeaters)
Connectors9-pin D-Sub (IP20) or M12 B-coded 5-pin (IP65/IP67)

Sources and scope

PI (PROFIBUS & PROFINET International) PROFIBUS Installation Guideline and IEC 61158 Type 3.

Record date:

Suggest a correction

Where is it used?

  • Maintaining and expanding installed process and discrete factory automation lines.
  • Connecting decentralized ET200-class I/O stations, encoders, and motor drives over long cable runs.
  • Migrating brownfield RS-485 instrumentation toward PROFINET via proxy gateways.

What are the common pitfalls?

  • Omitting active bus termination power at the physical ends of the RS-485 trunk (PROFIBUS requires powered 390/220/390-ohm pull-up/down termination, not just 120-ohm).
  • Creating unbuffered spur/stub cables at baud rates above 1.5 Mbps, which causes severe signal reflections.
  • Forgetting to keep shield continuity clamped cleanly to functional earth at entry points.